Products
Q3 Automatic Transfer Switch
  • Q3 Automatic Transfer SwitchQ3 Automatic Transfer Switch
  • Q3 Automatic Transfer SwitchQ3 Automatic Transfer Switch
  • Q3 Automatic Transfer SwitchQ3 Automatic Transfer Switch

Q3 Automatic Transfer Switch

Q3 Automatic Transfer Switch (hereinafter referred to as ATS), it is suitable for the power supply system of AC 50Hz, rated voltag f 400V, rated current of 63A and below. Choice and conversion between two power supply according to the needs. ATS have protection functions of overload, short circuit, under-voltage, but also have functions of fire, double breaking and output closing signal. Particularly applicable to the lighting lines in office buildings, shopping malls, banks, high-rise buildings and other places with needs of the fire.

Scope of Application

Q3 Automatic Transfer Switch (hereinafter referred to as ATS), it is suitable for the power supply system of AC 50Hz, rated voltag f 400V, rated current of 63A and below. Choice and conversion between two power supply according to the needs. ATS have protection functions of overload, short circuit, under-voltage, but also have functions of fire, double breaking and output closing signal. Particularly applicable to the lighting lines in office buildings, shopping malls, banks, high-rise buildings and other places with needs of the fire.

Q3 Automatic Transfer Switch complies with GB / T14048.11 standard.


Models and Specifications


Normal operating conditions and installation conditions

● The altitude of the installation site should not exceed 2000m.

● Ambient air temperature

Ambient air temperature does not exceed the upper limit is +40℃; the average ambient air temperature in 24h does not exceed +35℃. The ambient air temperature lower limit is not less than -5 ℃.

● Atmospheric conditions

○ Humidity

At the maximum temperature of +40℃, the air relative humidity is less than 50%, there is a higher relative humidity allowed at lower temperatures, for example, up to 90% at 20℃. Special measures should be taken for gel that is occasionally generated due to changes of humidity.

○ Pollution degree: 3

● Installation conditions

Installed in the place without shock and invasion of rain and snow ; the upper terminal connect to the power side, the lowr terminal connect to the load side; the inclination between products and vertical plane is not more than 5°.

● Installation category: Ⅲ

● The external magnetic field near the installation site does not exceed 5 times the geomagnetic field in any direction.


Technical parameter

Basic parameters of Q3 Automatic Transfer Switch see Table 1

Product performance parameters

Meet the standards

GB/T 14048.11

ATS class

CB class

Use categories

AC-33iB

Rated operating voltage Ue

AC230V-400V

Rated operating frequency

50Hz/60Hz

Rated operating current Ie

6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A 63A

Switching control voltage

AC230V

Rated insulation voltage Ui

AC690V

Conversion operation time

≤3s(Not adjustable, the factory has been adjusted)

Life

Electrical life

1500 times

Mechanaical life

6000 times

Rated short-time making capacity Icm

7.5kA

Rated short-time breaking capacity Icn

5kA


Basic parameters of terminal type and intelligent type of Q3 Automatic Transfer Switch in Table 2

Product model

Common type

Intelligent type

Installation method

Integral type

Integral type

Operation method

Automatic and manual

Automatic manual and

double breaking

Monitoring function

Phase failure detection

Common power supply

three-phase undervoltage,

lack phase and phase

failure detection

Conversion method

Automatic change and

automatic recovery

Automatic change and

automatic recovery

Fire linkage control

No

DC12-24V input

double breaking

(Automatic fire cut-off function)

Display function

LED light

LED light


Outline and mounting dimensions

Size 

Model and specification

Outline dimensions

Installation dimensions

L

W

H

L1

W1

Φd

Four-pole switch

220

132

120

200

120

5


Installation

Connection wire (cable) for ATS uses single core polyvinyl chloride (PVC) insulated copper wire or equivalent copper bar, the sectional area is selected according to the table 4.

Rated current In(A)

6

10

16 20

25

32

40 50

63

Sectional area of wire or copper bar mm²

1.0

1.5

2.5

4.0

6.0

10

16


Wiring diagram of ATS

Wiring diagram of four-pole switch


Wiring diagram of three-pole switch


Wiring diagram of ATS output terminals

Wiring diagram of commom type output terminals


Wiring diagram of intelligent type output terminals


Ordering Information

Users must specify when ordering:

7.1 Name and type of Q3 Automatic Transfer Switch;

7.2 The rated current (A) of Q3 Automatic Transfer Switch;

7.3 Poles (four-pole, the ATS is three-phase four-wire system when the customer does not indicate);

7.4 Controller type of Q3 Automatic Transfer Switch;

7.5 Quantity.

7.6 Customer requirements for Miniature Circuit Breakers DZ47 or C65

For example: ordering Q3 Automatic Transfer Switch, three-pole, rated current of 6A, common type, the number of 100 units. Can be written as: Q3-63 / 3P 6A 50 units.

Order Q3 Automatic Transfer Switch, four-pole, rated current of 63A, intelligent type, miniature circuit breakers require 50 DZ47D type. Can be written as: Q3-63 / 4P 63A DZ47D 100 units.



Hot Tags: Q3 Automatic Transfer Switch, China, Manufacturer, Supplier, Factory
Send Inquiry
Contact Info
We strive to provide customers with quality products. Request Information, Sample & Quote, Contact us!
X
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Privacy Policy
Reject Accept