The XUCKY Electronic circuit breaker ECB (External circuit breaker) product is designed for use in a variety of applications where precise control and monitoring of electrical systems are required. It is suitable for both commercial and industrial settings, including but not limited to power distribution systems, automation processes, and energy management solutions.
The XUCKY Electronic circuit breaker ECB (External circuit breaker) product is designed for use in a variety of applications where precise control and monitoring of electrical systems are required. It is suitable for both commercial and industrial settings, including but not limited to power distribution systems, automation processes, and energy management solutions. XUCKY ECB suitable for AC 50Hz/60Hz. under normal circumstances, the circuit breaker of the electric operation mechanism can be used for the infrequent conversion of the line and the infrequent start of the motor. The series of electric operation is small in size, easy to install, stable in operation, intuitive display, and can be operated manually. Its comprehensive performance has reached the advanced level of similar products in the world.
Classification
The ECB product falls under the category of intelligent electrical devices, specifically designed for monitoring and controlling electrical parameters. It can be classified as an advanced smart controller for electrical systems.
Intelligent Controller Performance
The intelligent controller within the ECB product offers superior performance in terms of data acquisition, processing, and response. Key features include:
● Real-time monitoring of voltage, current, power factor, and energy consumption
● Automated fault detection and alarms
● Remote access and control capabilities
● Customizable settings and thresholds for optimal system performance
Normal Working Conditions
To ensure reliable operation, the ECB product should be installed and operated under the following conditions:
● The ambient temperature is -5℃~+40℃In between, the altitude does not exceed 2,000 meters.
● Atmospheric conditions: the highest temperature is 40℃ The relative humidity of the air does not exceed 50%, and higher relative humidity can be allowed at lower temperatures, such as 20℃The time reaches 90%.。Special measures should be taken for the condensation caused occasionally due to temperature changes.
● The external magnetic field of the installation site shall not exceed in any direction.5 times the geomagnetic field, avoid large electromagnetic interference (such as high-power motors or frequency converters) near the product, no explosive and corrosive gases, no rain and snow invasion, dry and ventilated.
● The electric operating mechanism is between 85~110% of the rated operating voltage (24VDC, the voltage allowable range is 22.4~25.2VDC), which can ensure the reliable operation of the circuit breaker.
● Operating voltage: AC220V/DC220V, AC380V/DC380V, DC24V; a total of 3 operating voltages.
● P1 and P2 are the operating power supply access terminals. P1 and P2 must be isolated from the main circuit of the circuit breaker and can withstand voltage resistance of not less than AC2000V/1min between the main circuit and shall not break down and flashover. The detection voltage resistance instrument used complies with IEC60947-1 (GB14048) .1) Requirements
● S1, S2, S4 are the access end of the control line, and the signal is the pulse signal (short-term connection); the contacts on the table relay are connected to S1 (common point), S2 (close), S4 (open). When S1 and S2 are connected through the contacts on the table relay, the circuit breaker is closed (the closing command does not require the signal to be connected or disconnected to execute uniformly); when S1 and S4 are connected through the contacts on the table relay, the circuit breaker is split (the switch command does not require the signal to be connected or disconnected)
● When the automatic mode is switched to manually operate the circuit breaker to close or split the gate, the circuit breaker can close or split the gate. It is not affected by the on or disconnection signals of S1, S2 and S4.
● When the manual mode operation circuit breaker is closed or disconnected and switched to automatic mode, the circuit breaker does not need to operate according to the signal control mode, only re-operate the closing signal S1, S2 to turn on the circuit breaker to close (the closing command does not require the signal to be connected or disconnected); the switch S1, Deduction (the command does not require the signal to be connected or disconnected to execute).
● When the circuit breaker fails short-circuit tripping or tripping, the 1s self-reset function (automatic operation of the circuit breaker to the splitter position) will be delayed in automatic mode, which will not be controlled by the signal before tripping or tripping (the closing signal is uniformly connected or the gate signal is uniformly connected); only the re- The gate is closed (the closing command does not require the signal to be connected or disconnected uniformly); the gate S1 and S4 are connected to the circuit breaker (the gate command does not require the signal to be connected or disconnected for execution). In manual mode, there is no operation to close or split the circuit breaker.
Apperance description
Product Parameter Performance
Technical data
Frame current Inm (A)
250S
400S
630S
800S
1000S
Working voltage Ue (V)
400
Rated insulation voltage Ui (V)
AC1000
Rated impulse withstand voltage Uimp (KV)
8
Number of poles (P)
3
Rated current In (A)
100, 125, 140, 160,
180, 200, 225, 250
250, 315, 350, 400
400, 500, 630
630, 700, 800
800, 1000
Ultimate breaking capacity Icu (KA)
AC240V
35
35
65
65
65
AC415V
25
25
40
40
40
Operating breaking capacity Ics (KA)
AC240V
35
35
65
65
65
AC415V
25
25
40
40
40
Electrical life (times)
1000
1000
1000
500
500
Mechanical life (times)
7000
4000
4000
2500
2500
Operating voltage
AC230V(85%~110%)
Wiring
Up in and down out, down in and up out
Protection degree
IP30
Isolation function
Yes
Tripping type
Thermomagnetic
Accessories
Shunt, alarm, auxiliary
Certificate
CE
Hot Tags: Electronic Circuit Breaker ECB, China, Manufacturer, Supplier, Factory