AFDD-32 Series Arc Fault Protectors (AFDD)
  • AFDD-32 Series Arc Fault Protectors (AFDD)AFDD-32 Series Arc Fault Protectors (AFDD)

AFDD-32 Series Arc Fault Protectors (AFDD)

XUCKY's arc-protected type B + residual current operated circuit breaker (Af-rcbo-RRB- protects against arc, residual current, over-under voltage, overload transients, etc. , it is recommended to use in the places with dense personnel and inflammable materials, such as home, school, nursing home, hotel, historic buildings and so on.

AFDD-32 Series Arc Fault Protectors (AFDD)

AFDD-32 Series Arc Fault Protectors (AFDD)

integrate Type B+ residual current protection


Dear users:

First of all, thank you for choosing the products of Wenzhou XUCKY Electric Co.,Ltd .

Wenzhou XUCKY Electric Co.,Ltd combines the needs of customers and the market, based on scientific and technological innovation, to product stability, effectiveness, practicality as a tool, to serve users for the purpose of product research and development, strive to achieve the maintenance-free products, so as to better serve users and serve the community.

This manual mainly introduces the performance, function, operation, installation and wiring of the Arc Fault Protector produced by our company. Please read the instruction carefully before using this circuit breaker.

If you have any questions about this manual, or if you have any questions or requests in the application, you can contact us through the following ways, we will respond and solve them in time.

This product conforms to:

GB/T 31143-2014 General requirements for ARC protection appliances (AFDD)

GB/T 16917.1-2014  Residual current operated circuit breakers (rcbos) with overcurrent protection for household and similar purposes-part 1: General Rules

GB/T 16917.22 Residual current operated circuit breakers (rccbs) with overcurrent protection for household and similar purposes-part 2.2: General Rules for the applicability of operating functions to rcbos relating to line voltages

GB/T 22794-2017 Type F and Type B residual current operated circuit breakers without and with overcurrent protection for household and similar purposes


Product description

XUCKY's arc-protected type B + residual current operated circuit breaker (Af-rcbo-RRB- protects against arc, residual current, over-under voltage, overload transients, etc. , it is recommended to use in the places with dense personnel and inflammable materials, such as home, school, nursing home, hotel, historic buildings and so on.


Product type and meaning

AFDD-32 Series Arc Fault Protectors (AFDD)


Technical parameters

◆ Rated working voltage(Un): AC230V

◆ Rated operating frequency: 50Hz±2%

◆ Rated insulation voltage(Ui): 440V

◆ Rated shock resistance(Uimp): 4KV

◆ Rated current(In): 6A、10A、16A、20A、25A、32A

◆ Normal power consumption: <0.4W

◆ Type of instantaneous release: Type C

◆ Ability to operate short circuits(Ics): 6KA

◆ Rated short circuit capacity(Icn): 6KA

◆ Rated residual current action value: 30mA

◆ Type of residual current: B+type

◆ Current limit level: 3

◆ Mechanical life: 20000cycles

◆ Electrical life: 10000cycles

◆ Operating temperature: -25℃ ~ +65℃

AFDD-32 Series Arc Fault Protectors (AFDD)


Product characteristics

1. Fault arc detection

XUCKY uses a high-speed and high-precision sampling ADC to extract key information about electrical parameters, such as arc occurrence time, arc amplitude, arc duration, etc. , the neural network algorithm has better generalization ability and higher discrimination accuracy under big data, and it can distinguish normal arc and fault arc, ensure no leakage and no error.


The tripping characteristics are shown in the following table:

Function

Reference standards

Technical specifications

Specific requirements

ARC failure

GB/T 31143

The arc current discriminates the limit value

3A:1s

6A:0.5s

13A:0.25

20A:0.15s

40A、63A:0.12s

75A:12(0.5sMaximum half wave number allowed)

100A:10(0.5sMaximum half wave number allowed)

150A、200A、300A、500A:8(0.5sMaximum half wave number allowed)


Tripping curve:

AFDD-32 Series Arc Fault Protectors (AFDD)


2.Residual current protection

This product implements B+ type residual current protection function, which can identify residual current faults of different frequency AC (150KHz), pulsating DC, smooth DC and their composite situations.

Type of residual current

Residual current waveform

Application scenarios

Type AC

AFDD-32 Series Arc Fault Protectors (AFDD)50Hz AC

Residential: incandescent lamp, electric heater, water heater, oven, vacuum cleaner, etc.

Type A

AFDD-32 Series Arc Fault Protectors (AFDD)

Ac-type base with added pulsating DC superimposed smooth DC

Residential:commercial construction: such as induction cooker, microwave ovens, Dishwasher office: all kinds of computers

Type F

AFDD-32 Series Arc Fault Protectors (AFDD)

The type a base increases the compound wave residual current

Residential: inverter air-conditioning, inverter washing machine business construction: air-conditioning, swimming pool inverter pumps, heating pumps

Type B

AFDD-32 Series Arc Fault Protectors (AFDD)

F-type foundation increases AC and DC smoothness within 1 khz

Industry: Crane, driving

civil: charging piles, elevators

Type B+

AFDD-32 Series Arc Fault Protectors (AFDD)

B-base increases communication within 150 khz

Civil, commercial construction: frequency conversion equipment, high-frequency to earth leakage fire


The tripping characteristics are shown in the following table:

Function

Reference standards

Technical specifications

Specific requirements

Residual current protection

GB/T 16917.1

GB/T 22794

Type of residual current action

Type B+

Rated residual action current

30mA

Break time

I△n:0.3s

2I△n:0.15s

5I△n:0.04s

5A~200A、500A:0.04s


Tripping curve:

AFDD-32 Series Arc Fault Protectors (AFDD)


3.overcurrent protection

This product uses high-precision chips to accurately collect real-time current in the circuit. With calibration and temperature compensation mechanisms, it is minimally affected by environmental temperature changes, ensuring high accuracy and reliable overload protection. The instantaneous trip selection is primarily based on magnetic trip, with electronic trip as a backup, providing a dual safety measure of electromagnetic and electronic trip.

The tripping characteristics are shown in the following table:

Function

Reference standards

Technical specifications

Specific requirements

Overload protection

GB 10963.1

Tripping characteristics

Type C

1.13In:Power on for 1H without tripping

1.45In:Power on for 1H tripping

2.55In:1s< Release time<60s

5In:Power on 0.1 s without tripping

10In:Release time<0.1s


Tripping curve:

AFDD-32 Series Arc Fault Protectors (AFDD)


4.Over-voltage protection

The over-voltage and under-voltage protection of this product uses high-precision sampling circuit to accurately judge whether the voltage reaches the threshold, and immediately open the circuit, to avoid voltage fluctuations damage home appliances.

The tripping characteristics are shown in the following table:

Function

Reference standards

Technical specifications

Specific requirements

Overpressure

JB/T 12762


Action setting value

275V

Action time

250V:Do not move

275V:3s<Drive time≤15s

300V:1s<Drive time≤3s

350V:0.25s<Drive time≤0.75s

400V:0.1s<Drive time≤0.2s

Under pressure

Action setting value

50V~160V

Action time

0.6s~5s


Tripping curve:

AFDD-32 Series Arc Fault Protectors (AFDD)AFDD-32 Series Arc Fault Protectors (AFDD)


5.Equipment self-test

This product has manual detection function. Long press the detection button "T" on the surface of the switch, and the switch will automatically generate residual current detection signal and fault arc signal. When two kinds of fault signals are detected, the switch is disconnected and the self-test is successful; If there is a self-test failure, the switch is constantly on, four indicators are steady on, the circuit breaker itself is faulty, need to replace the circuit breaker. The manual detection function of this product needs to be pressed once a month to ensure timely detection of equipment faults and ensure user safety.

This product has automatic detection function. When the switch is powered on for the first time or every 1 hour of continuous operation, automatic fault arc detection is carried out inside the equipment. The self-test is successful, and the equipment continues to work; The self-test fails, the switch is constantly on, the four indicators are steady on, the circuit breaker itself is faulty, and the circuit breaker needs to be replaced. 5.Failure indication

Indicator light status information

This product is equipped with 4 LED indicator lights, each indicator lamp respectively by off, always bright, flashing three kinds of shape. The information represented by the different indicator states is shown in the following table

Lights

Normal

Transient overload

Fault arc

Residual current

Overpressure

Equipment failure

1

p

 

 

 

2


p

 

 

3


 

p

 

4

 

 

 

p



○:Extinguish ●:It's always on  p:Twinkle



6.Troubleshooting

Please contact the professional for troubleshooting when the fault indicator shows that there is a fault, or when the product is off-loaded due to other unknown reasons。

Type of failure

Cause of failure

Troubleshootig

Transient overload

Excessive use of electrical equipment, excessive load

1. Turn off the load on the back end of the product and press the reset button to restore it to normal.


Fault arc

Insulation aging, breakage; poor contact

Disconnect all electrical appliances and connect to each one individually until a fault is found.

After finding the faulty electrical appliance, first off and then in accordance with the following steps: 1) after the first observation of electrical appliances external wire aging, broken; bad contact terminal.

observe whether the connecting part between the wire and the electric appliance, the wire and the plug is loose or not.

if no abnormality is found in the above two steps, please further investigate the internal problems of electrical appliances.

If a switch trip occurs regardless of the use of any electrical appliance and the indicator shows information about the fault arc, try using a different plug or socket. Please replace the socket if the socket is out of order. Please replace the socket if the socket is out of order.

4, repeat the above steps still can not solve the problem, please check the indoor distribution lines.

Residual current

1. The human body touches the live part to produce the residual current

The equipment insulation fault to the ground residual current

3. The line is damaged, to the ground residual current

 1, people or animals electrocuted lead to release, make people or animals away from the electrified equipment after re-closing the switch, press the reset button, indicator lights no longer alarm.

2, equipment to the ground residual current: Unplug all electrical appliances, re-close the switch, in order to test each electrical appliances separately. Find out and disconnect the fault electrical appliances, press the reset button no longer alarm.

3. Seek further investigation and disposal by qualified professionals.

Overpressure and underpressure

High front-end voltage caused by direct lightning

High front-end voltage caused by distribution line fault

Inductance in the circuit, capacitor components produce resonance

4, circuit load current (such as large equipment start) caused by under-voltage.

1, respectively detect the front-end voltage, if the front-end voltage abnormal contact manufacturers or maintenance personnel for circuit maintenance.

2, the back-end voltage is abnormal, after disconnecting the electrical appliances, long press the T key, replace the electrical application scene.

3, some large-scale equipment start-up when the existence of over-voltage phenomenon, after closing this kind of equipment long press t key no longer alarm.

 

LN exchange


Faulty wiring results in a reverse zero-wire connection


1. Use a multimeter to locate the zero-fire line.

2, the front-end zero-wire connection, disconnect the front-end power connection.

3, the back end of the zero-wire connection is reversed, after the switch is broken, the connection is positive。

Equipment failure

There is an internal fault in the equipment

Contact relevant staff to repair or replace the equipment.

Other malfunctions

Other indicator lights do not indicate fault trip

Contact relevant staff to repair or replace the equipment.


Installation and wiring

1 External dimensions (in mm)

AFDD-32 Series Arc Fault Protectors (AFDD)


2 Installation size (in mm)

AFDD-32 Series Arc Fault Protectors (AFDD)

Figure 6.2 installation dimensions


3 wiring diagram (in mm)

Suitable for copper wire connection below 10mm2.

The following table shows the rated current and the cross-sectional area of the connecting wire.

Rated current A

6

10

16

20

25

32

Section area of conductormm2

1

2.5

4

6

6

10

AFDD-32 Series Arc Fault Protectors (AFDD)


4 switch on and off

Note:

(1) the size of terminal is 5mm × 8mm (the relation between conductor area and rated current: Delisi) .

(2) the length of the entry port is 8mm ± 1mm.

(3) the incoming line ends with the power supply and the outgoing line ends with the load.

(4) during installation, insert the equipment into the installation rail as shown in the installation dimension drawing, and do not loosen it.

(5) the handle is closed up and disconnected down.

(6) press the“T” button several times after electrifying to judge whether the equipment is normal or not. The indicator content information is detailed in the fault indication


Usage notes

a) this product is an electronic-mechanical one-piece product, without user-adjustable components, and can not be disassembled or adjusted at will during use.

b) when wiring, should pay attention to the circuit breaker nominal voltage, rated current. And can not exceed the nominal voltage or the maximum allowable current to avoid the device frequently off, affecting the use of users.

c) the cross-sectional area of the wire connecting to the circuit breaker should meet the requirement of the load current to avoid the heat damage caused by poor contact or too thin wire. In addition, the wiring must be fastened and fastened.

d) when wiring, should pay attention not to connect the incoming and outgoing line wrong.

e) when wiring, select the copper wire matching the rated current.

f) installation, maintenance and maintenance should be performed by qualified personnel.

g) after tripping due to break, overload, short circuit, etc. , professional should be found to remove the fault and then resume closing, so as not to affect the service life of the product or cause danger.

h) this product protection grade IP20, does not have the dust-proof function, in the dust more applications, please install in the well-sealed terminal box. I) if the product is found broken or abnormal sound when unpacking, please stop using and contact the manufacturer in time.

i) please make a Waste treatment when the product is scrapped. Thank you for your cooperation.

AFDD-32 Series Arc Fault Protectors (AFDD) Be aware of danger!!!

j) do not use wet hands to operate AFDD.

k) do not touch conductive parts in use.

l) ensure that the product is not electrified during maintenance.

m) do not use short circuit to test the product.


Maintenance

 Maintenance and maintenance, must have a professional qualification personnel to operate;

 When maintaining and maintaining, it is necessary to ensure that the product is not electrified;

 Under normal operating conditions, maintenance and maintenance once a year (press the test button once a month) , maintenance as shown in the table below.

Project

Content

Appearance

No dust, no condensation, if need to clean; no damage; no color change of shell segment

Terminal connection

Button torque 2.0N.m tight, not loose

Handle closing/opening operation

The operation should be flexible


Transportation and storage

A) the transportation and unpacking of circuit breakers shall not be subjected to severe impact and shall be in accordance with the provisions of JB/T 9329-1999“Basic environmental conditions and test methods for the transportation and storage of instruments and instruments”.

B) store the circuit breaker in the original packing box at the ambient temperature of -25 ° C ~ + 55 ° C. The relative humidity shall not exceed 85% , and shall not contain in the air gases sufficient to cause corrosion, dry, ventilated, dustproof, away from fire sources and not be wet by rain.

C) this product is a solid-state static equipment, there is no user-adjustable internal components, the use does not need to open the shell.


Repair and replacement

Under the conditions of normal installation, application and inspection of the products, if the products are damaged or can not work normally due to the manufacturing quality within 12 months after delivery from the manufacturer, the manufacturer replaces the repair gratuitously for the user, exceeds the warranty period, must pay the repair.

However, if damage is caused by:

(1) due to improper use, maintenance and storage;

(2) self-modification, improper maintenance;

(3) after the purchase due to fall and damage in the course of installation;

(4) earthquake, fire, lightning strike, abnormal voltage and secondary disasters and other irresistible force.


Statement

The contents of this instruction may need to be changed due to design improvement. Wenzhou XUCKY Electric Co.,Ltd reserves the right to amend this instruction without prior notice. The company shall not be liable for any loss of life or property caused by improper use, maintenance or safekeeping of the goods in violation of any notice.